01
Approach temperature tells the story
The difference between condensing temperature and ambient air, and between chilled water out and evaporating temperature, shows how well the plant is transferring heat. A rising approach on a clean-looking machine usually means fouling, low charge or poor water flow.
Recording those numbers each visit builds a trend, and a trend catches drift months before a trip or a lockout does.
02
Water side and airflow
Condensers blocked with dust, pollen or leaves lose capacity quickly in a dusty plant room or near trees. Coil cleaning is simple, cheap and the single largest efficiency gain on an air-cooled chiller.
On the water side, untreated circuits scale and corrode, and strainers block. Checking water treatment and cleaning strainers prevents most pump and heat-exchanger problems.
03
Controls, safeties and staging
Safety devices exist to protect the compressor, so a chiller that trips repeatedly is telling you something rather than misbehaving. Bypassing a safety is never the repair.
Check that compressors stage and unload as designed, that sensors read correctly, and that the set points still match how the building is used. Buildings change, and a schedule set for a full office often runs unchanged through a decade of fit-outs.