01
Icing is a symptom with three common causes
Restricted airflow, low refrigerant charge and a control or sensor fault account for almost every iced-up unit we attend. Each looks similar from outside and needs a different fix, which is why replacing a sensor before checking airflow wastes money.
On a heat pump, frost on the outdoor coil in heating mode is normal and clears itself. Frost that never clears, or ice building into a solid block, is a fault rather than a cycle.
02
Airflow first
A blocked filter, a closed return, a collapsed flexible duct or a coil packed with dust drops the coil below freezing. It is the most common cause in homes near trees and in kitchens where grease settles on the coil.
Cleaning the filter and coil and confirming the return path is open often resolves it entirely. If icing returns within days, move on to the refrigerant check.
03
Charge, sensors and drains
A slow leak lowers coil pressure and temperature until the coil ices even with good airflow. Charge should be confirmed by pressure and temperature measurement, not by topping up gas and hoping.
Coil and ambient sensors drift, and a unit that never enters or exits defrost correctly will ice regardless of charge. Drains matter too: water that cannot leave the tray freezes and builds a block into the coil.